Configuration and startup of EtherNet/IP™
Configuration of the EtherNet/IP™ master
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
41
5. Click [OK].
ð The following window is displayed.
18014400474821899
6. In the edit box [1], enter the name of the EtherNet/IP™ interface with which the
data are stored in the controller tags.
7. Enter the IP address of the EtherNet/IP™ interface field in the edit box [3].
8. Select data format "Data-INT" or "Data-SINT" from the drop-down list [2].
ð The process data always contains 16 bits (INT). The maximum number of pro-
cess data is 120 (for "Comm format" DATA-INT) or 240 (for "Comm format"
DATA-SINT).
9. Enter the following connection parameters in the section [5]:
Window element Value
Input Assembly Instance 173
Output Assembly Instance 163
Configuration Assembly Instance 1
Input Size 16
Output Size 16
Configuration Size 0
10. Activate the check box [4].