6
Configuration and startup of EtherNet/IP™
Configuration of the EtherNet/IP™ master
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
45
10. Select the communication format and the process data arrangement.
ð You can select up to 120PI/PO (process input data/process output data words)
with 16 Bit respectively. The device usually uses 8 PI/PO for communication
with the internal power section "PFA-..." and the PLC. By selecting the data
type SINT, a data array with 16 bytes is created by the software.
11. Click [OK].
ð The previous window opens.
12. Open the tab [1].
15117198347
13. Enter the cycle time (data rate) in the edit box [2]. The device supports a cycle
time of a minimum of 4 ms. Longer cycle times can be implemented without any
problems.
14. Choose the input type from the drop-down list [3]. Depending on the network con-
figuration, e.g. if a redundant fieldbus master or an HMI keypad are integrated in
the network, you can either select "Unicast" or Multicast" connection.
15. Click [OK].
ð The device is included in the project and the settings are adopted.
16998413/EN – 12/2016