11. Save the project and transfer it to the PLC.
12. Enter the following controller tags values:
19132375179
Controller tag Value
WriteParameter_Start 1
WriteParameter_Request.Index Index of the parameter to be described.
WriteParameter_Data Value to be written in the parameter.
WriteParameter_Request.SubAddress 1 20
WriteParameter_Request.SubChannel 1 3
WriteParameter_Request.SubAddress 2 0
WriteParameter_Request.SubChannel 2 0
13. Switch to RUN mode of the PLC.
ð The write request is executed once.
ð If the write request is answered, the controller tag "WriteParameter_Re-
sponse.Index" displays the written index. The controller tags "WritePara-
meter_Response.Data_HIGH" and "WriteParameter_Response.Data_LOW"
contain the written data.
ð In this example, the parameter P302 maximum speed is set to 3000min
-1
.