72 FLOWSIC100 Flare-XT · Operating Instructions · 8023761/V 1-0/2020-10 · © SICK Engineering GmbH
Installation FLSE100-XT
Fig. 37 Marking on probe version F1F-P
Align the measuring path of probe version F1F-P as shown, see → Fig. 37. The
maximum deviation of the rotation angle of the probe to the flow direction may be ±3°.
To ensure this, use a laser to align probe version F1F-P:
Flow direction