Operating instructions Chapter 4
S300
8010948/YY96/2016-02-17 © SICK AG • Industrial Safety Systems • Germany • All rights reserved 49
Subject to change without notice
Configurable functions
Static complementary sampling
Using the two control input pairs on the S300 Advanced 2
2
= 4 monitoring cases can be
s
witched, using the three control input pairs on the S300 Professional and Expert 2
3
=
8
monitoring cases can be switched.
Using external inputs (e.g. those of a Flexi Soft safety controller, see section 4.5 “Inputs”
on page 37), 2
5
= 32 monitoring cases can be switched via maximally five control input
pairs.
A B C D E E.g. case
0 0 0 0 0 1
1 0 0 0 0 2
0 1 0 0 0 3
1 1 0 0 0 4
0 0 1 0 0 5
1 0 1 1 0 6
0 1 1 0 0 7
1 1 1 0 0 8
… …
0 1 1 1 0 15
1 1 1 1 0 16
0 0 0 0 1 17
… …
0 1 1 1 1 31
1 1 1 1 1 32
Undefined input information will result in the S300 switching the OSSDs to the OFF state
or signaling Protective field infringed via EFI.
complementary evaluation
Note