EasyManua.ls Logo

Siemens Cerberus CS1140 - Page 246

Siemens Cerberus CS1140
250 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
B2Q191 Logging printer
246
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
Set baud rate 9600, default value in the CS1140 (AlgoWorks)
Function Programming switch S1
S1-1 S1-2 S1-3 S1-4 S1-5 S1-6 S1-7 S1-8
Baud rate 300
closed closed closed
1200
open closed closed
2400
closed open closed
9600
open open closed
Baud rate 19200
closed closed open
2 Programming switch "S1": Setting –> character set
Setting character set 'ISO Latin 1'
ISO Latin 1 supports the languages: English, German, Italian, Spanish, Portuguese, Danish, Fin-
nish, Swedish, Norwegian, Dutch and Flemish
Function Programming switch S1
S1-1 S1-2 S1-3 S1-4 S1-5 S1-6 S1-7 S1-8
Character set ISO Latin 1
ISO Latin 2
ISO Latin 3 *
ISO Latin 4 *
ISO Latin 5
ISO Greek
ISO Arabic
ISO Hebrew
Character set ISO Cyrillic
* ISO Latin 3 and ISO Latin 4 are not supported by the control unit
Character set ISO –> generates the following (permanent) communication parameters:
1 start bit
8 data bits
no parity
1 stop bit
3 Link "X11 + "X12": Connection "K3" , or "A1"/"A3" and "A2" active
Header (Micro) «A3»
(HCMOS) is active if:
jumpers "X11" and "X12"
are inserted in connectors
1-2 and the jumpers
"X13" and "X14" are
inserted in connectors 1-2
A1
A2
X11
X12
X14
X13
A3
K3
Header «A2» (TTL)
is active if:
links "X11" und "X12"
are inserted in con-
nectors 1-2, "X13"
and "X14" are not
relevant
Interface «K3» (RS232 /
V28) is active if:
links "X11" und "X12" are
inserted in connectors 2-
3, "X13" and "X14" are
not relevant
4 Ribbon header "A1" (14-pin): 0-modem connection –> no function for CS1140
5 Ribbon header "A2" (14-pin): TTL port for modem card K1D... or 3
rd
party mo-
dem (V28,FSK,PSK)
6 Link "X13 + "X14": Connection "A3" port 2 or "A3", port 3 active
7 Ribbon header "A3" (20-pin, micro): 0-modem connection for internal housing
connection to AlgoPilot
8 Plug-in terminals "K3": Connection RS232 / V28
9 LED indicator block "State printer"
green Main program in operation
yellow Motor blocked
green Printing on/off
H1H2
1
2
yellow Paper end

Table of Contents