ng the batteries and power supply
12
187 |
Building Technologies
Operating currents, processor unit (FC2080)
Consumer Type I
R
[mA] I
A
[mA] Qty. I
R total
I
A total
Notes
Processor unit (FC2080)
● ↑ CPU card (FC2080)
incl. network module
(SAFEDLINK, CC)
● Communication card
(FC2080) incl.
network module
(SAFEDLINK, CC)
FCC2002-A1
180
110
180
110
1
1
290 290 Basic components
● Slot 1: CPU card
(FC2080)
● Slot 3: Communication
card (FC2080)
Redundant CPU card
(FC2080)
FCC2004-A1 180 180 Optional, slot 2
I/O card (RT) FCI2007-A1 70 70 Optional, slot 4
(without load)
Module bus card 1
1
Optional, slot 4
Instead of I/O card (remote
transmission)
Module bus card 2
1
Optional, slot 5
Total, optional operating
unit
2
For supply via FC2080
Total, processor unit
Quiescent current = I
R total
Alarm current = I
A total
__ __ __ __ Total < 8 A
Table 58: Operating currents, processor unit (FC2080)
1
According to separate table for module bus cards
2
According to separate table for optional operating unit