Project planning of
indication and operation devices
EVAC
-
NL indicators [NL]
5
46 | 242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
Remote EVAC
Figure 7: EVAC-NL remote in separate housing
1 External housing
2 Operating add-on FCM2008-N1 with 20-zone EVAC indicator
FTO2007 EVAC-NL operating unit
FTI2002 EVAC-NL connector board (mimic display)
FCA2002 RS485 module on the control panel PMI & mainboard
The EVAC-NL indicator can also be operated in a separate housing, e.g., in an Eco
housing, at a distance of up to 1000 m from the station. In this case the EVAC-
NL operating unit FTO2007-N1 is connected via an additional connector board
FTI2002-N1 to the RS485 module on the PMI & mainboard.
The supply comes via the fire control panel or via a separate supply.
Peripheryboard
FTO2007
PMI & Mainboard
FCM20xx
FTO2007
RS485
FCA2002
FTI2002
FC20xx
Vsys
RS485
Vext.
FTI2002
X1
X1
X1
X1
X4
X4
FCM2008-N1
1
2
X400
X402