Project planning of indication and operation devices
EVAC
-
NL indicators [NL]
5
47 |
242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
Mimic display driver (EVAC)
Figure 8: EVAC-NL remote as mimic display
1 External housing
2
LED mimic display panel (34 LED connections, 16 outside buttons
and 1 key switch)
FTO2007 EVAC-NL operating unit
FTI2002 EVAC-NL connector board (mimic display)
FT2003 Mimic display driver (EVAC)
The EVAC-NL indicator can also be operated as a remote mimic display at a
distance of up to 1000 m from the station. The EVAC-NL mimic display driver
FT2003-N1 consists of the additional connector board FTI2002-N1 and an EVAC-
NL operating unit FTO2007-N1 without indicator panel.
The mimic display driver FT2003-N1 is fitted in a customer-specific housing, and
the associated LED displays are arranged according to the layout plan. The
connection is made to the RS485 module on the control panel PMI & mainboard.
The supply comes via the fire control panel or via a separate supply.
Periphery board
PMI & mainboard
FCM20xx
RS485
FCA2002
FTI2002
FC20xx
Vsys
RS485
Vext.
FTO2007
FT2003
1
2
X1
X4
X1
X5
X2/X3