Planning detector lines
Planning an FDnet detector line
7
83 |
242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
7.1.9.4 Diagram for line cards with four loops or four stubs
This diagram serves to verify the maximum current connection factor reserve
(MK_res) for line cards with connections for four loops or four stubs. The
following line cards are affected by this:
Integrated line card with loop extension (operation of four loops)
Integrated line card without loop extension (operation of four stubs)
Line card (FDnet) FCL2001-A1 (operation of four loops or four stubs)
Conditions
Max. 63 devices per loop or stub
Only loops or stubs are operated on all connections.
Figure 28: Maximum current connection factor reserve (MK_res) for the operation of four loops or
four stubs