Planning detector lines
Planning an FDnet detector line
7
84 | 242
Building Technologies
008843_v_en_
--
Fire Safety
2015
-
-
15
7.1.9.5 Diagram for line cards with eight stubs
This diagram serves to verify the maximum current connection factor reserve
(MK_res) for line cards on which eight stubs are operated. The following line
cards are affected by this:
Integrated line card with loop extension (operation of eight stubs)
Line card (FDnet/C-NET) FCL2001-A1 (operation of eight stubs)
Conditions
Max. 31 devices per stub
Only stubs on all connections
Figure 29: Maximum current connection factor reserve (MK_res) for the operation of eight stubs