6 Configuring with STEP 7 or a GSDML File
102
IE/ASINTERFACE LINK PN IO as of hardware version 1, as of firmware version V2.0
Release 08/2018
C79000G8976C21603
Slot assignment in the configuration table of HW Config
The configuration table in the station window of HW Config shows the slot
assignment of the IE/AS-i LINK. The first column “AS-i addr.”shows the AS-i
address. The first AS-i address 0 is used for the IE/AS-i LINK itself or for the AS-i
line 1 substitute. As of firmware version 2.0, slot 0 is divided into four rows:
S Row 1, AS-i addr. “[1]”:
Proxy for the configuration of the specific AS-i line properties, [1] is the name of
the AS-i line.
S Row 2, AS-i addr. “X1”:
Proxy for the configuration of the PROFINET properties of the LAN interface of
the module
S Row 3, AS-i addr. “X1 P1”:
Proxy for the configuration of Ethernet port 1
S Row 4, AS-i addr. “X1 P2”:
Proxy for the configuration of Ethernet port 2
After slot 0, the following slots are assigned placeholder modules for 62 A/B slaves
(AS-i addr. of the I/O modules: 1A, B, 2A etc.). With a double master, the number
of the AS-i line is preceded by square brackets (AS-i addr.: [1]:1A, [1]:B, [1]:2A
etc.).
With a double master, the placeholder module 31B is followed by the proxy for AS-i
line 2 with the name “[2]”. This is followed in turn by the placeholder modules for
the 62 slaves of line 2 (AS-i addr.: [2]:1A, [2]:B, [2]:2A etc.).
The placeholder modules have the default configuration FFFF
H
so that they
already have priority in the AS-i slave settings configured on the IE/AS-i LINK
module.
Parameter Assignment for the IE/AS-i LINK
By double-clicking on the IE/AS-i LINK (icon in the PROFINET IO system), you
open the properties dialog of the IE/AS-i LINK. Here, you can set the following
parameters:
S “General” Tab
Setting the PROFINET device name of the module
Setting the device number
Entering a comment
The “Assign IP address via IO Controller” option is enabled in the default
settings.
S “Identification” tab
If required, you can assign the plant designation and the location identifier for
the module in this tab.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET IE/AS-INTERFACE LINK PN IO and is the answer not in the manual?

Siemens SIMATIC NET IE/AS-INTERFACE LINK PN IO Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET IE/AS-INTERFACE LINK PN IO
CategoryControl Unit
LanguageEnglish

Related product manuals