5 Display / WBM Configuration
72
IE/ASINTERFACE LINK PN IO as of hardware version 1, as of firmware version V2.0
Release 08/2018
C79000G8976C21603
5.2.9.4 SNMP
WBM: “SNMP” tab Configuration of SNMP for an IE/AS-i LINK
Note
To be able to access additional AS-i parameters of the IE/AS-i LINK from a central
management station, you require the private MIB.
The private MIB is located on the IE/AS-i LINK.
Procedure:
In your Internet Browser, enter the following for “Address”:
<IP address of the device>/doc/snAsi.mib
Save the displayed file with File > Save As... and select the path, file name and
“text file” for the file type and enter MIB as the extension.
On this page, you make the basic settings for SNMP.
If an alarm arrives, the IE/AS-i LINK can send traps (alarm messages) to up to two
different (network management) stations at the same time. Traps are sent only for
events that were specified in the “Events” tab. The IE/AS-i LINK supports SNMP
V2.
Parameter Function
Enable SNMP Enables/disables the SNMP function.
SNMP read-only Enables/disables write-protection for SNMP variables.
Read Community
String
Editable display of the user name for read access to SNMP variables.
Write Community
String
Editable display of the user name for write access to SNMP variables. Here, you
can only make modifications if write protection (SNMP read-only) has been
disabled.
Enable traps Enables/disables the trap function.
IP address Here, you enter the addresses of the stations (SNMP manager no. 1/2) to which the
IE/AS-i LINK will send traps (you simply need to enter an address).
Enable Select this option to enable sending of traps to the required stations (SNMP
manager no. 1/2).
Notice
For security, change the community strings. Resetting the device also means re-
setting the password to the factory settings.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET IE/AS-INTERFACE LINK PN IO and is the answer not in the manual?

Siemens SIMATIC NET IE/AS-INTERFACE LINK PN IO Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET IE/AS-INTERFACE LINK PN IO
CategoryControl Unit
LanguageEnglish

Related product manuals