EasyManua.ls Logo

Siemens SIMATIC NET IE/AS-INTERFACE LINK PN IO

Siemens SIMATIC NET IE/AS-INTERFACE LINK PN IO
193 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Using the Data Record Interface
158
IE/ASINTERFACE LINK PN IO as of hardware version 1, as of firmware version V2.0
Release 08/2018
C79000G8976C21603
8.2.2.7 Read_Actual_Configuration
Meaning
This call reads the following configuration data (CDI) of an addressed AS-i slave
obtained by the AS-i master on the AS-Interface.
S I/O configuration
S ID code
S ID1 code
S ID2 code
The configuration data is specified by the manufacturer of the AS-i slave. The
meaning of the configuration data is described in /2/.
Structure of the RecordDataRead service Index 11
Byte Meaning
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Version_hi = 0x00
1 Version_lo = 0x00
2
I/O configuration ID code
3 ID1 code ID2 code

Table of Contents

Related product manuals