8 Using the Data Record Interface
127
IE/ASINTERFACE LINK PN IO as of hardware version 1, as of firmware version V2.0
Release 08/2018
C79000G8976C21603
8.2.1 AS-i Line Calls
8.2.1.1 Store_Actual_Parameters
Meaning
This call writes the current parameters of the AS-i slaves from the volatile memory
of the AS-i master to its retentive memory. If the C-PLUG is inserted, the data is
written only to the C-PLUG. Existing value are overwritten, in other words, the
parameters of all AS-i slaves are configured.
In the factory setting, the bits of the AS-i slave parameters on the AS-i master all
have the value 1.
The RecordDataWrite service index 7 does not contain any user data.
For information on “parameters” and the IDs of the “Configuration” (I/O
configuration, ID code, ID1 code and ID2 code) /5/.
Exceptions
There are some AS-i slave types with which the AS-i master itself manages the
slave parameter assignment. The configured parameters for these AS-i slaves are
always the same F
H
.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET IE/AS-INTERFACE LINK PN IO and is the answer not in the manual?

Siemens SIMATIC NET IE/AS-INTERFACE LINK PN IO Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET IE/AS-INTERFACE LINK PN IO
CategoryControl Unit
LanguageEnglish

Related product manuals