5 Display / WBM Configuration
71
IE/ASINTERFACE LINK PN IO as of hardware version 1, as of firmware version V2.0
Release 08/2018
C79000G8976C21603
5.2.9.3 E-mail
To use this service, port 25 of the relevant server must be opened.
WBM: “E-Mail” tab monitoring the network with E-mails
The IE/AS-i LINK provides the option of sending an E-mail when an alarm occurs
(for example to the maintenance technician). The E-mail contains the identification
of the sending device, a description of the cause of the alarm in plain language and
a time stamp with the system time. This allows simple, central network monitoring
for networks with few nodes based on an E-mail system. When E-mail alarm
messages arrive, the sender is identified and the browser starts WBM to read out
further diagnostic information. The requirements for sending E-mails are as
follows:
S The E-mail function on the IE/AS-i LINK is enabled and the E-mail address of
the recipient is configured.
S The E-mail function is enabled for the relevant event,
S there is an SMTP server in your network that can be reached by the IE/AS-i
LINK,
S The IP address of the SMTP server is entered on the IE/AS-i LINK.
Parameter Function
Enable E-mail Enables/disables the E-mail function.
Recipient Here, enter the E-mail address to which the IE/AS-i LINK sends an E-mail if a fault
occurs.
SMTP server
IP address
Here, enter the IP address of the SMTP server over which the E-mail is sent.
SMTP server
IP port
IP port via which the mail is sent.
Sender Freely selectable sender address of the E-mail.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET IE/AS-INTERFACE LINK PN IO and is the answer not in the manual?

Siemens SIMATIC NET IE/AS-INTERFACE LINK PN IO Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET IE/AS-INTERFACE LINK PN IO
CategoryControl Unit
LanguageEnglish

Related product manuals