8 Using the Data Record Interface
157
IE/ASINTERFACE LINK PN IO as of hardware version 1, as of firmware version V2.0
Release 08/2018
C79000G8976C21603
8.2.2.6 Get_Permanent_Configuration
Meaning
This call reads the following configuration data (configured desired settings: PCD)
of an addressed AS-i slave.
S I/O configuration
S ID code
S ID1 code
S ID2 code
This data is read from the EEPROM of the AS-i master or from the C-PLUG, if this
is inserted.
The configuration data is specified by the manufacturer of the AS-i slave. The
meaning of the configuration data is described in /2/.
Structure of the RecordDataRead service Index 9
Byte Meaning
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Version_hi = 0x00
1 Version_lo = 0x00
2
I/O configuration ID code
3 ID1 code ID2 code