EasyManuals Logo

Siemens SIMATIC NET IE/AS-INTERFACE LINK PN IO User Manual

Siemens SIMATIC NET IE/AS-INTERFACE LINK PN IO
193 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #157 background imageLoading...
Page #157 background image
8 Using the Data Record Interface
157
IE/ASINTERFACE LINK PN IO as of hardware version 1, as of firmware version V2.0
Release 08/2018
C79000G8976C21603
8.2.2.6 Get_Permanent_Configuration
Meaning
This call reads the following configuration data (configured desired settings: PCD)
of an addressed AS-i slave.
S I/O configuration
S ID code
S ID1 code
S ID2 code
This data is read from the EEPROM of the AS-i master or from the C-PLUG, if this
is inserted.
The configuration data is specified by the manufacturer of the AS-i slave. The
meaning of the configuration data is described in /2/.
Structure of the RecordDataRead service Index 9
Byte Meaning
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Version_hi = 0x00
1 Version_lo = 0x00
2
I/O configuration ID code
3 ID1 code ID2 code

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET IE/AS-INTERFACE LINK PN IO and is the answer not in the manual?

Siemens SIMATIC NET IE/AS-INTERFACE LINK PN IO Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET IE/AS-INTERFACE LINK PN IO
CategoryControl Unit
LanguageEnglish

Related product manuals