6 Configuring with STEP 7 or a GSDML File
110
IE/AS−INTERFACE LINK PN IO as of hardware version 1, as of firmware version V2.0
Release 08/2018
C79000−G8976−C216−03
Below slot 0 or 100 for the AS-i lines, the AS-i slave modules are mapped to the
following 63 slots. With a single master, these are slots 1...31 and 33...63 (or
101...131 and 133...163 for a double master).
The slot number in HW Config corresponds to the AS-i address.
The assignments are as follows:
S AS-i line 1
− Slot 1...31 corresponds to AS-i slave address 1...31 or 1A...31A.
− Slot 33...63 corresponds to AS-i slave address 1B...31B.
S AS-i line 2
− Slot 101...131 corresponds to AS-i slave address 1...31 or 1A...31A.
− Slot 133...163 corresponds to AS-i slave address 1B...31B.
The GSDML file occupies all slots with one digital module 1 byte I/O (1 byte
DI / DO). The slave modules have the default configuration FFFF
H
so that they
already have priority in the AS-i slave settings configured on the IE/AS-i LINK
module.
Parameter Assignment for the IE/AS-i LINK
By double-clicking on the IE/AS-i LINK (icon in the PROFINET IO system), you
open the properties dialog of the IE/AS-i LINK. Here, you can set the following
parameters:
S “General” tab
Here, you can assign the PROFINET device name and the device number,
enable the option “Assign IP address via PROFINET IO Controller” and enter a
comment.
S “IO Cycle” tab
Here, you can change the update time for the IO cycle and the number of
update cycles with missing I/O data.
Configuring the Properties of the AS-i Line
To set the address and diagnostic parameters for the AS-i line, double-click on the
row of the corresponding line proxies in the configuration table. The Properties
dialog of the AS-i line opens. Here, you can make the following entries:
S “General” tab
Here, you can see the name, Order number and hardware and software version
of the module. You can enter a comment in the input box.
S “Addresses” tab
Here, you can change the diagnostic address.