Configuring environment
6.2 Creating configuration data
Expanding the user interface
Commissioning Manual, 11/2006, 6FC5397-0DP10-0BA0
6-5
Example of COMMON.COM
[MMC_DOS]
sc101=tooth.com ; MACHINE
sc111=mda.com ; The files are stored on the flash memory of
the HMI.
sc122=auto.com
sc207=param.com ; PARAMETER
sc314=aeditor.com ; PROGRAM, Editor
sc315=aeditor.com
sc316=aeditor.com
sc407=dienste.com ; SERVICES
sc507=diagnose.com ; DIAGNOSIS
sc607=inbetrn.com ; STARTUP
sc826=cmm.com ; ShopMill, Machine, AUTO
sc857=cmm.com ; Messages / alarms
sc858=cmm.com
sc867=cmm.com ; Tools, WO
CHK_COMMON.COM=1 ; Rapid execution of the HMI
LOGSIZE=30 ; Size of the error log (LOG file) 30 KB
[PLC_SELECT] ; Notification of displays, which can be called
by the PLC
PC1= CYC82, drilling.com ; Fig. 1:
PC2= CYCLE90, millthre.com ; Fig. 2:
6.2.3 Configuring start softkeys
Overview
The start softkeys named here can be used to activate the associated configuration files.
The possible start softkeys for dialogs are predefined. Additional start softkeys are not
possible. Start softkeys are specific to operating areas.
Programming
Syntax SCxxx =
File
Identifier Softkey connection: Connection between softkey and configuration file
"xxx" represents an internal softkey identity of the start softkey.
Parameter
File
Name of configuration file