Configuring the system
2.4 PCU 50.3 with SITOP UPS module
PCU-Basesoftware (IM8)
Commissioning Manual, 03/2009, 6FC5397-1DP10-4BA0
49
Required settings on the UPS module (USB interface)
On - Off
1
+2V
2
+1V
3
+0.5V
Cut-in threshold
+22V (fixed)
4
+1V
5
+1V
6
+0.5V
7
+0.2V
8
+0.2V
9
+0.1V
End-of-charge voltage
+ 26.3V fixed
10
0.35A / 0.7A Charging current
On - Off
1
Set time/max. time
2
+320 s
3
+160 s
4
+80s
5
+40 s
6
+20 s
7
+10 s
Buffer time
+5 s fixed
8
Disconnection
9
Accumulator operating state on/off
Legend:
Delivery condition setting
Setting for operation on the PCU 50