Parameterizing/addressing
9.4 Description of parameters
SIPART PS2 with and without HART
184 Operating Instructions, 10/2013, A5E00074631-11
d4.FACT3 - factor 3
Use this sub-parameter to set the factor for the formation of limit threshold 3. Set the factor in
a range from "0.1" to "100.0". The limit threshold is the product of "d1.LIMIT" and
"d4.FACT3".
The threshold 3 error message is displayed when the limit threshold 3 is exceeded. The
process to activate and display this error message is described in the "XDIAG" parameter.
The factory setting is "10.0".