Parameterizing/addressing
9.4 Description of parameters
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
187
F2.LEVL2 - threshold 2
Use this sub-parameter to set a threshold in percent. Use threshold 2 to monitor the lower
hard end stop. Set the threshold in a range from "0.1" to "10.0".
The positioner triggers a fault message if the difference between the lower hard end stop
and the initialization value undershoots threshold 2. The process to activate and display this
fault message is described in the "XDIAG" parameter.
The factory setting is "2.0".
F3.LEVL3 - threshold 3
Use this sub-parameter to set a threshold in percent. Use threshold 3 to monitor the lower
hard end stop. Set the threshold in a range from "0.1" to "10.0".
The positioner triggers a fault message if the difference between the lower hard end stop
and the initialization value undershoots threshold 3. The process to activate and display this
fault message is described in the "XDIAG" parameter.
The factory setting is "4.0".