EasyManuals Logo

Siemens SIPART Series User Manual

Siemens SIPART Series
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #195 background imageLoading...
Page #195 background image
Parameterizing/addressing
9.4 Description of parameters
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
193
J4.LEVL3 - threshold 3
Use this sub-parameter to set a threshold in "°C" or "°F". Use threshold 3 to monitor the
upper limit temperature. Set the threshold in a range from "-40.0C" to "90.0C" or "-40.0F" to
"194.0F".
The positioner triggers a fault message if the current temperature inside the enclosure
exceeds threshold 3. The process to activate and display this fault message is described in
the "XDIAG" parameter.
The factory setting is "90.0C".

Table of Contents

Other manuals for Siemens SIPART Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART Series and is the answer not in the manual?

Siemens SIPART Series Specifications

General IconGeneral
BrandSiemens
ModelSIPART Series
CategoryAccessories
LanguageEnglish

Related product manuals