Parameterizing/addressing 
  9.4 Description of parameters 
SIPART PS2 with and without HART 
Operating Instructions, 10/2013, A5E00074631-11 
199 
When the time interval expires, the calculated reference average is shown on the display. 
 
Note 
Current position average 
The respective current position average is displayed in the "19.PAVG" diagnostics 
parameter. If no position average has been calculated, "COMP" is displayed in the 
"19.PAVG" 
diagnostics parameter. 
The factory setting is "IdLE". 
Use this sub-parameter to set threshold 1 for the maximum deviation of the current position 
average from the reference average. Set the threshold in a range from "0.1" to "100.0". 
The positioner triggers an error message if the difference between the position average and 
the reference average exceeds threshold 1. The procedure to activate and display this error 
message is described in the "XDIAG" parameter. 
The factory setting is "2.0". 
Use this sub-parameter to set threshold 2 for the maximum deviation of the current position 
average from the reference average. Set the threshold in a range from "0.1" to "100.0". 
The positioner triggers an error message if the difference between the position average and 
the reference average exceeds threshold 2. The procedure to activate and display this error 
message is described in the "XDIAG" parameter. 
The factory setting is "5.0". 
Use this sub-parameter to set threshold 3 for the maximum deviation of the current position 
average from the reference average. Set the threshold in a range from "0.1" to "100.0". 
The positioner triggers an error message if the difference between the position average and 
the reference average exceeds threshold 3. The procedure to activate and display this error 
message is described in the "XDIAG" parameter. 
The factory setting is "10.0".