EasyManua.ls Logo

Siemens SIPART Series - Page 201

Siemens SIPART Series
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameterizing/addressing
9.4 Description of parameters
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
199
When the time interval expires, the calculated reference average is shown on the display.
Note
Current position average
The respective current position average is displayed in the "19.PAVG" diagnostics
parameter. If no position average has been calculated, "COMP" is displayed in the
"19.PAVG"
diagnostics parameter.
The factory setting is "IdLE".
P3.LEVL1 - threshold 1
Use this sub-parameter to set threshold 1 for the maximum deviation of the current position
average from the reference average. Set the threshold in a range from "0.1" to "100.0".
The positioner triggers an error message if the difference between the position average and
the reference average exceeds threshold 1. The procedure to activate and display this error
message is described in the "XDIAG" parameter.
The factory setting is "2.0".
P4.LEVL2 - threshold 2
Use this sub-parameter to set threshold 2 for the maximum deviation of the current position
average from the reference average. Set the threshold in a range from "0.1" to "100.0".
The positioner triggers an error message if the difference between the position average and
the reference average exceeds threshold 2. The procedure to activate and display this error
message is described in the "XDIAG" parameter.
The factory setting is "5.0".
P5.LEVL3 - threshold 3
Use this sub-parameter to set threshold 3 for the maximum deviation of the current position
average from the reference average. Set the threshold in a range from "0.1" to "100.0".
The positioner triggers an error message if the difference between the position average and
the reference average exceeds threshold 3. The procedure to activate and display this error
message is described in the "XDIAG" parameter.
The factory setting is "10.0".

Table of Contents

Other manuals for Siemens SIPART Series

Related product manuals