Alarm, error, and system messages 
  10.2 Diagnosis 
SIPART PS2 with and without HART 
Operating Instructions, 10/2013, A5E00074631-11 
213 
12 PRPST - time since the last partial stroke test 
This parameter shows the elapsed time in days since the last partial stroke test. In addition, 
the following status messages can be displayed: 
●  notSt - No Test 
A manual partial stroke test has not yet been executed. 
●  SdtSt - Stopped Test 
The last Partial-Stroke-Test was interrupted.  
●  FdtSt - Failed Test 
The last partial stroke test has failed. 
13 NXPST - time until the next partial stroke test 
This parameter shows the time in days until the next partial stroke test. The requirements are 
that the partial stroke test is activated in the configuration menu and a test interval is set. If 
one of the above-mentioned conditions is not met, "OFF" is shown on the display. 
14 DEVI - general control valve fault 
This value provides information about the present dynamically determined deviation from the 
model response. If the underlying function is deactivated in the configuration menu, "OFF" is 
displayed. 
15 ONLK - pneumatic leakage 
This parameter shows the current leakage indicator. If the leakage detection is deactivated in 
the configuration menu, "OFF" is displayed. 
16 STIC - static friction/slipstick effect 
This parameter shows the filtered value of the stroke magnitude in percent resulting from the 
static friction. If the function is deactivated in the configuration menu, "OFF" is displayed. 
17 ZERO - zero point displacement 
Display of the current displacement of the lower hard end stop with respect to its initialization 
value. The activation of the "down tight closing function" is a condition to determine this. 
Activate using the "YCLS" parameter in the configuration menu. If the underlying function is 
deactivated in the configuration menu, "OFF" is displayed. 
18 OPEN - displacement of upper end stop 
Display of the current displacement of the upper hard end stop with respect to its initialization 
value. The activation of the "up tight closing function" is a condition to determine this. 
Activate using the "YCLS" parameter in the configuration menu. If the underlying function is 
deactivated in the configuration menu, "OFF" is displayed.