Alarm, error, and system messages 
  10.2 Diagnosis 
SIPART PS2 with and without HART 
Operating Instructions, 10/2013, A5E00074631-11 
217 
45 WT00 bis 52 WT95 - number of operating hours in the actuating ranges WT00 to WT95 
When the positioner is in the automatic mode, statistics regarding the duration for which a 
valve or a flap operated in a particular section of the actuating range are continuously 
maintained. The entire actuating range is divided into 8 sections from 0 to 100 %. The 
positioner records the current position continuously and increments the runtime meter 
assigned to the corresponding actuating range every hour. This helps in drawing conclusions 
about the past operating conditions and especially in assessing the control properties of the 
control loop and the entire control valve.  
The actuating range is divided as follows: 
 
Actuating range section [%] 
Division of actuating range 
You can simultaneously set the eight operating hours counters to zero. To do this, press the 
 button for at least 5 seconds. 
 Since the actuating ranges are provided at the end of the diagnostics menu, press the 
 decrement button several times along with the   button. This will help you in accessing 
the diagnostics numbers faster. 
 
Note 
Updating of the diagnostics values 
All diagnostics valu
es are updated in the non-volatile memory every 15 minutes so that, in 
case of a power failure, only the values of the previous 15 minutes may be lost. 
 
Description of parameters 13 through 33 (Page 164)