Alarm, error, and system messages
10.3 Online diagnostics
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
221
Error message disappears
when
12 Yes Static friction/
Slipstick effect
d. STIC≠OFF ... Slipjumps can no longer be
detected, or the function is
Increased static friction, valve
no longer moves smoothly,
13 Yes Temperature
undershot
H. TMIN≠OFF ... the lower temperature
thresholds are no longer
Ambient temperature too low
14 Yes Temperature
J. TMAX≠OFF ... the upper thresholds are
Ambient temperature too high
15 Yes Position average
deviates from the
reference value
P. PAVG≠OFF ... the position average
calculated after a comparison
interval is again within the
thresholds for the reference
value, or the function is
In the last comparison
interval, the valve trajectory
was changed so severely that
a deviating position average
was calculated.
1)
Refer to the corresponding parameter descriptions for additional information about parameters
Overview of parameters 1 to 5 (Page 149)
Overview of parameters 6 to 51 (Page 150)