Addr. Parameter Function C Setting Options Default Setting Comments
611 Spont. FltDisp. Device, General YES
NO
NO Spontaneous display of
flt.annunciations
613A Gnd O/Cprot. w. P.System Data
1
Ignd (measured)
3I0 (calcul.)
Ignd (measured) Ground Overcurrent
protection with
614A OP. QUANTITY 59 P.System Data
1
Vphph
Vph-n
V1
V2
Vphph Opera. Quantity for 59
Overvolt. Prot.
615A OP. QUANTITY 27 P.System Data
1
V1
Vphph
Vph-n
V1 Opera. Quantity for 27
Undervolt. Prot.
616 STATIC GEN. P.System Data
1
YES
NO
NO Static or non self-exc.
Asyn. Generator
640 Start image DD Device, General image 1
image 2
image 3
image 4
image 5
image 6
image 1 Start image Default
Display
651 ParEN100(LC)blk Device, General OFF
ON
OFF DIGSI-config. over EN100
(LC) blocked
660 IP adr[0](Prim) Device, General 0 .. 255 0 IP address [0] (NTP-
Primary)
661 IP adr[1](Prim) Device, General 0 .. 255 0 IP address [1] (NTP-
Primary)
662 IP adr[2](Prim) Device, General 0 .. 255 0 IP address [2] (NTP-
Primary)
663 IP adr[3](Prim) Device, General 0 .. 255 0 IP address [3] (NTP-
Primary)
664 IP adr[0] (Sec) Device, General 0 .. 255 0 IP address [0] (NTP-
Sekundary)
665 IP adr[1] (Sec) Device, General 0 .. 255 0 IP address [1] (NTP-
Sekundary)
666 IP adr[2] (Sec) Device, General 0 .. 255 0 IP address [2] (NTP-
Sekundary)
667 IP adr[3] (Sec) Device, General 0 .. 255 0 IP address [3] (NTP-
Sekundary)
668 Client activ Device, General OFF
ON
OFF Client activ
669 Daylight Set Device, General OFF
ON
OFF Daylight Set
670 Offset TZ/min Device, General -1440 .. 1440 min 60 min Offset for time zone in
minutes
671 Offset DayT/min Device, General -1440 .. 1440 min 60 min Offset for daylight in
minutes
672 W2S month Device, General 1 .. 12 3 month of time set winter
to summer
673 W2S week Device, General 1 .. 5 5 week of time set winter
to summer
Functions, Settings, Information
F.2 Settings
SIPROTEC 4, 7SJ80, Manual 477
E50417-G1140-C343-A8, Edition 12.2017