SWT 3000 Equipment Manual Technical Data
© SIEMENS AG 2008 Edition p3_3_2x 08/09 Page - 5
Transmission time (SWT 3000 stand alone)*
Broad band equipment
Single purpose
Alternate multi purpose F2
< 10ms (F6, CT)
< 15ms (F6, CT)
Narrowband equipment < 15ms (F6)
* Values are given for the IFC-P module. If the IFC-D module is used all specified signal transmission delays are pro-
longed by about 4 ms
Operation via the PLC system ESB 2000i will prolong the transmission time by about 4ms
Transmission time (SWT 3000 integrated into PowerLink)*
Broad band equipment
Single purpose
< 10ms (F6, CT)
Alternate multi purpose
F2 + AMP
Alternate multi purpose
DP + AMP
Simultaneous multipurpose
< 15ms (F6, CT)
< 19ms (F6, CT)
< 10ms (F6, CT)
Narrow band equipments
Using speech-plus band < 19ms (F6, CT)
*Values are given for the IFC-P module. If the IFC-D module is used all specified signal transmission delays are prolonged
by about 4 ms
Operation via the PLC system ESB 2000i will prolong the transmission time by about 4ms