EasyManua.ls Logo

Siemens SWT-3000 - Selecting the Operating Mode; Selecting the Connection Interface

Siemens SWT-3000
267 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Commissioning SWT 3000 Equipment Manual
Selecting the operating mode
The following settings are possible:
Table 45: Selection of the operating modes
Operating mode Comment
Mode 1 (double system protection) Possible with all variants
Mode 2 (single-phase protection) Not possible with the variants VF2, VF4 and IF2.00k1
Mode 3 (switching functions) Not possible with the variants VF2, VF4 and IF2.00k1
Mode 3a (4 independent commands) Only possible with the variants VF1_CT resp VF3_CT
Mode 3b (2 plus 2) Only possible with the variants VF1_CT resp VF3_CT
Mode 4 (only one command active) Not possible with the variants VF2, VF4 and IF2.00k1
Mode 5A (3 independent commands) Only possible with the variant VF[x] M5A or IF[x] M5A
The setting <stand alone> for a stand alone device or <integrated> for a device integrated in the
PowerLink must also be made with the <System> menu.
The teleprotection signaling parameter is set as <Single-purpose> for standalone devices. The
setting <Alternate multipurpose> is also possible in conjunction with PLC systems depending on
the configuration and parameters of the PLC system).
Selecting the connection interface
The menu option <Connection analog resp. digital> offers the following setting options:
Table 46: Connection options of the PU3f module
Connection analog Comment
off
No analog interface
CLE
(only with system setting <stand alone>)
Standalone devices with cable connection, or connection to a
PLC system via the CLE module
via CSP (dig)
If integrated in the PowerLink system
FOM-1 analog
Stand alone device with FOM connection to a PowerLink
system
Connection digital
X.21 DTE / DCE
Digital interface X.21 DTE or DCE
G703.1 DTE / DCE
Digital interface G703.1 64kbps DTE or DCE
G703.6 DTE / DCE
Digital interface G703.6 2Mbps DTE or DCE
FOM 64k DTE / DCE
Fibre optic connection between two SWT 3000 with 64kbps
FOM 2M DTE / DCE
Fibre optic connection between two SWT 3000 with 2Mbps
FO-Box 64k
Fibre optic connection to the FO-Box bit rate 64kbps
FO-Box 2M
Fibre optic connection to the FO-Box bit rate 2Mbps
The menu option <Reflection> ; “Yes “ or “No “ offers the additional option of reflecting the
received command if there is no local energizing (setting “Yes”).
This setting is only evaluated by the device in the operating modes ”Mode 1 (Double system pro-
tection)“ or “Mode 2 (Single-phase protection)“. In these modes the fourth binary input of the
IFC-D/P module can be used for excitation. In the operating mode “Mode 3 (Switching functions)“
this input is provided for the fourth command. If
continuous commands are transmitted with the
device, you must also activate the option
“Continuous signaling ;. In this case the device
sends the guard tone for 180 ms at cyclical intervals so that a connection can be re-established
automatically after a line interruption or failure of a device. In this case the
command output time
must be increased accordingly
(see timer settings).
All settings made are accepted by the program by choosing <Apply>. If you click on <Cancel> the
previous setting are retained. With <OK> the settings are accepted and the input tab is closed.
Page - 48 Edition p3_3_2x 08/09 © SIEMENS AG 2008

Table of Contents

Related product manuals