Technical Data SWT 3000 Equipment Manual
Page - 10 Edition p3_3_2x 08/09 © SIEMENS AG 2008
Insulation Withstand Voltage
VF input/output 500 Vrms
Power supply 2,5 kVrms
Command input / output 2,5 kVrms
Alarm outputs 2,5 kVrms
Digital input / output
G703.1
G703.6 sym.
500 Vrms
500 Vrms
Impulse Withstand Level 1,2/50µs
VF input / output 1 kV
Digital input / output 1 kV
Power supply 5 kV
Command input / output 5 kV
Alarm outputs 5 kV
Climatic Conditions
During operation -5°C to + 55°C
During storage and transport -40°C to +70°C
Relative humidity 5 – 95%
max. abs. humidity (no condensation) 29 g/m
3
Mechanical Conditions
Degree of protection IP 20
Vibration 5 – 9 Hz: 1,5 mm amplitude
9 – 200 Hz:
0,5 g acceleration
Shock 10 g acceleration
International Standards
Performance and testing of teleprotection transmis-
sion equipments of power systems
IEC 60834-1 second edition 1999-10
Power supply and electromagnetic compatibility IEC 60870-2-1
Environmental conditions IEC 60870-2-2
Product safety EN 60950