SWT 3000 Equipment Manual Functional Description
© SIEMENS AG 2008 Edition p3_3_2x 08/09 Page - 23
Mode 3b (2plus2)
The commands 1 and 2 are always uncoded transmitted. The commands 3 and 4 as well as com-
binations from commands 3 and 4 with 1 and 2 are always coded transmitted.
Table 9: Logic scheme for the Mode3b (2plus2)
activated
Input
Transm.
uncoded
Transm.
coded
Command output in the remote station
all off fg ---
BI1 f1 CO1
BI2 f2 CO2
BI1 + BI2 f3 CO1 + CO2
BI3 f
s
+f
4
CO3
BI4 f
s
+f
5
CO4
BI3 + BI4 f
s
+f
6
CO3 + CO4
BI1 + BI3 f
1
+f
4
CO1 + CO3
BI1 + BI4 f
1
+f
5
CO1 + CO4
BI1 + BI3 + BI4 f
1
+f
6
CO1 + CO3 + CO4
BI1 + BI2 + BI3 f
1
+f
7
CO1 + CO2 + CO3
BI2 + BI3 f
2
+f
4
CO2 + CO3
BI2 + BI4 f
2
+f
5
CO2 + CO4
BI2 + BI3 + BI4 f
2
+f
6
CO2 + CO3 + CO4
BI1 + BI2 + BI4 f
3
+f
4
CO1 + CO2 + CO4
BI1 + BI2 + BI3 + BI4 f
3
+f
5
CO1 + CO2 + CO3 + CO4
Usynch f
s
+f
7
---
Mode4 (only one commands active)
Table 10: Logic scheme for the Mode4
activated
Input
Transm.
uncoded
Transm.
coded
Command output in the remote station
all off fg fg ---
BI1 f1 f
s
+f
4
CO1
BI2 f2 f
1
+f
4
CO2
BI3 f3 f
2
+f
4
CO3
BI4 f4 f
3
+f
4
CO4
more than 1
input activated
fg
1)
fg ---
--- --- --- Alarm signaling
2)
USYNC fs f
s
+f
5
---
1) Input error. If more than one input is activated fg is transmitted.
2) If an invalid frequency or code is received, resp. in case of guard tone alarm

Table of Contents