EasyManua.ls Logo

Siemens SWT-3000 - Jumper Settings for the SWT 3000 Modules

Siemens SWT-3000
267 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Commissioning SWT 3000 Equipment Manual
Jumper settings for the SWT 3000 modules:
Jumper settings for the IFC modules
X41
X54
K1
K2
K3
K4
K8
K7
K6
K5
K9
K10
K11
K12
K16
K15
K14
K13
X42
IFC-D: K1 . . . K4
IFC-P: K13 . . . K16
IFC-S: K5 . . . K12
X53
X52
X51
X50
X49
X48
X47
X46
X45
X44
X43
BI 1
BI 3
BI 4
BI 2
X58
X57
X56
X55
S1
H1 H5
H2
H3
H4
H6
H7
H8
H10
H9
Control logic
1
2
3
4
X30
X40
1
1
Test operation
display
Operating LED
Figure 8: Position of jumpers X43 to X58
Table 19: Assignment of jumpers X43 to X58
Signal input 250V 110V 48/60V 24V
BI1
X55=inserted
X43=open
X44=open
X45=open
X55=open
X43=inserted
X44=open
X45=open
X55=open
X43=open
X44=inserted
X45=open
X55=open
X43=open
X44=open
X45=inserted
BI2
X56=inserted
X46=open
X47=open
X48=open
X56=open
X46=inserted
X47=open
X48=open
X56=open
X46=open
X47=inserted
X48=open
X56=open
X46=open
X47=open
X48=inserted
BI3
X57=inserted
X49=open
X50=open
X51=open
X57=open
X49=inserted
X50=open
X51=open
X57=open
X49=open
X50=inserted
X51=open
X57=open
X49=open
X50=open
X51=inserted
BI4
X58=inserted
X52=open
X53=open
X54=open
X58=open
X52=inserted
X53=open
X54=open
X58=open
X52=open
X53=inserted
X54=open
X58=open
X52=open
X53=open
X54=inserted
The second interface module is used in the case of an IFC-D/P module for doubling the output
contacts. The binary inputs are connected at only one module (in slot IFC-1).
In the case of module IFC-S jumpers X43- X58 are not provided because the binary inputs
are not existing. The module contains 8 signaling relays. For seven relays one changeover con-
tact is brought out in each case. The contact of relay K5 can be used as a make contact or a break
contact by means of jumper X42. All eight signaling contacts have a common root (3A1).
The jumper X30 serves for the switch over to the programming of the controller. In normal op-
eration the jumper must be in position 1-2. The connector X40 serves for the connection of the
programming device.
Page - 20 Edition p3_3_2x 08/09 © SIEMENS AG 2008

Table of Contents

Related product manuals