6 Using the product
138
10. Either
• click on [Finish] if the alarm message should not be
forwarded if the alarm is not acknowledged or
- The wizard is closed and the new rule is added to the list of
alarm messages.
• the With lack of confirmation, forward to if the alarm
message is to be forwarded to another recipient.
- The min input field for entering the time interval after which
the alarm message should be forwarded is shown along
with the selection list for determining the next recipient.
11. In the min field, enter the interval after which the alarm
message should be forwarded. (Time between the alarm being
sent to recipient 2 and it being forwarded to recipient 3).
12. Determine the receiver who is to receive the alarm message in
the to selection list.
The output targets (SMS or e-mail) for receiver 1 and
receiver 2 must not vary. For all receivers in an alarm
chain, the same output target (all SMS or all e-mail)
must be set, otherwise the alarm chain is interrupted.
13. Click on [Finish].
- The wizard is closed and the new rule is added to the list of
alarm messages.
14. Exit "Alarm Management" menu.
- Alarm settings are transferred to the devices.
Pos: 153 /TD/Produ kt verwenden/testo Sa veris/04 Alarme konf igurieren/PRO/03 Alar mübersicht @ 1\mod_119 8162959421_79.doc x @ 6863 @ 3 @ 1