5 First steps
72
3. Connect the USB cable to the computer.
4. Via Start | All Programs | Testo | Testo Saveris Ethernet
Wizard, open the wizard for entering the connection settings.
5. Follow the wizard's instructions and assign the IP address for
the Saveris base.
see Installing Saveris software, page 51
Pos: 79 /TD/Erst e Schritte/testo Saver is/Hardware erwei tern/02 Converter einbi nden/00 Converter ei nsetzen @ 1\mod_119755060 7093_79.docx @ 6315 @ 35 @ 1
5.14.3. Integrating Saveris converter (optional)
If the distance between the radio probe or router is too large for a
radio transmission, you can integrate a Saveris converter into the
measuring system. The converter is connected to the Saveris base
by means of an Ethernet cable and converts the radio signals to
Ethernet signals.
The measurement data of up to 15 radio probes/routers
can be transmitted with the converter to the Saveris
base.
You can connect several converters to the Saveris base
using a so-called switch. In this context, note that a
maximum of 150 probes can be connected or 450
measurement channels recorded at the Saveris base.
The preparation for the commissioning of a converter is
performed as with a Saveris Ethernet probe; see
Connecting the network cable., page 74 up to and
including see Connecting Ethernet probe with the
Saveris base, page 80