Remote Control
195
- Set: Res:Set:Phase:Select [Winding],[Phase1],[Phase2],[Phase3]
[Winding] = HV ¦ LV ¦ TV
[PhaseX] = 0 ¦ 1
Res:Set:Phase:Select [Phase]
[Phase] = 1 ¦ 2 ¦ 3
- Query: Res:Set:Phase:Select?
HV,[Ph1],[Ph2],[Ph3];LV,[Ph1],[Ph2],[Ph3];TV,[Ph1],[Ph2],[Ph3]
Res:Set:Current
Sets and returns the measuring current in Ampere for the three different windings (HV, LV
and TV).
- Set: Res:Set:Current [Winding],[Current]
[Winding] = HV ¦ LV ¦ TV
[Current] = 0.0 … 32.0
- Query: Res:Set:Current?
HV,[Current];LV,[Current];TV,[Current]
Res:Set:Current? [Winding]
[Current]
• Res:Data:R ¦ Res:Data:U ¦ Res:Data:I ¦ Res:Data:T
Returns the recorded value for all or certain windings and phases as 1.23456e-3
Resistance (R), Voltage (U), Current (I) or Temperature (T)
- Query: Res:Data:R?
[ResHV1],[ResHV2],[ResHV3],[ResLV1],[ResLV2],[ResLV3],
[ResTV1],[ResTV2],[ResTV3]
Res:Data:R? LV
[ResLV1],[ResLV2],[ResLV3]
Res:Data:R? TV,2
[ResTV2]
• Res:Meas:R ¦ Res:Meas:U
Returns the currently measured resistance values as 1.23456e-3. In automatic mode R1
and R2 are