To change the auto sequencing settings:
1. From the Setup System Operation Menu, use the arrows to
choose Auto Sequencing, then press Enter.
Activate or Deactivate
1. In the Activate / Deactivate screen, use the arrows to choose one
of three options:
a. ON for intervals of every 1 to 99 days, then press Enter and
proceed to Step1. below.
b. 12h for an interval of every 12hours, then press Enter and
proceed to Step1. below.
c. OFF to deactivate auto sequencing, then press Enter to
return to the previous menu.
Specify Start Time and Interval: Every 1 to 99 Days
1. Select the interval for how often the sequencing should occur in
the Every03 Daysfield. The default is 3 days; valid entries range
from 0 to 99 days.
For each digit, use the arrows to choose a number from 0 to
9, then press Enter to advance to the next digit.
When finished, press Enter to set the time of day.
Specify Start Time: Every 12 Hours
1. Specify the time of day the sequencing should begin in the
At00:00 field. The format is HH:MM for hours and minutes.
Use the arrows to choose from available entries for hours (00-23), then press Enter to
advance to minutes.
Use the arrows to select minutes (00-59).
When finished, press Enter again.
7.10.2 Turn Standby Testing On or Off
Standby testing permits scheduling an automatic operational check of devices in Standby mode.
When this feature is activated (ON), the Liebert AC8 tests all devices in Standby mode by putting each
device in operating mode for a designated time. If an operating unit is designated as disabled on alarm,
the unit is turned off during standby testing, then turned on when the test ends.
You may specify the time of day the testing begins, the duration of the test and the interval between
tests. Standby testing is OFF (deactivated) by default.
To change the standby testing settings: