EasyManua.ls Logo

Vertiv Liebert AC8 - Set up Mapping for a Digital Input

Vertiv Liebert AC8
174 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Use the following instructions to set up the mapping of each digital input or analog sensor
input to each relay.
7.11.1 Set Up Mapping for a Digital Input
Use the arrows to choose Map Input To Relay from the Map
Input/Sensor Menu, and press Enter.
From the Select Input Menu, choose the input you want—for
example, Device_1—and press Enter.
On the Input-to-Relay Map screen, you may map the selected
input to either or both of the control relays (1-2). The example at
right shows Device_1 mapped to Control Relay1.
To make changes to the mapping:
If needed, press Enter to advance to the position directly
below the relay.
Use the arrows to choose Y (Yes - Mapped to this relay) or
N (No - Not mapped), then press Enter.
Press Enter to advance to the next position where you
want to make a change.
Use the arrows to choose Y (Yes - Mapped to this relay) or
N (No - Not mapped), then press Enter.
When finished, press Enter again.
Default Mappings - Digital Inputs to Control Relays
By default, digital inputs are not mapped to any control relay, as shown in Table 7.17 below.
Digital input By default, mapped to control relay:
Device_1 (none)
Device_2 (none)
Device_3 (none)
Device_4 (none)
Device_5 (none)
Device_6 (none)
Device_7 (none)
Device_8 (none)
Table 7.17
Default mapping of digital inputs to relays
Vertiv | Liebert® AC8 User Manual | 102

Table of Contents

Related product manuals