• Press Enter to proceed, or Escape to cancel the entry. If you make a change, a confirmation
message appears: “Command Successful.”
Change Modem Hang Up Delay After a Call
• At the Change Modem Hang Up Delay After a Call prompt, enter the number of seconds to
delay hanging up after a call. The maximum is 99 seconds. The current setting appears in
brackets—[10] in the following example.
>CHANGE MODEM HANG UP DELAY AFTER A CALL(99 SEC MAX).
>[10]
>[
>COMMAND SUCCESSFUL
Press Enter to proceed, or Escape to cancel the entry. If you make a change, a confirmation message
appears: “Command Successful.”
7.8.3 Pager Setup - Pager Number and PIN
The Liebert AC8 may be configured to dial numeric or alphanumeric pagers when an alarm is detected.
You may enter up to four pager numbers—all configured pagers will be dialed each time an alarm occurs.
For each configured pager, you must enter the pager number to be dialed and the pager’s Personal
Identification Number (PIN).
See Liebert AC8 Specifications on page107 for supported pager settings.
The Liebert AC8 can send numeric or alphanumeric messages to supported pagers, as shown in the
following example:
When an alarm is detected, the first pager number is dialed—up to three times, if needed. After a
successful page or three dialing attempts, the next pager number is dialed, again with three attempts as
needed, and so on for all configured pagers.
Result of Page Action Message Generated
Successful Liebert AC8 dials next configured pager. —
Unsuccessful due to:
Busy signal / no answer /
no dial tone
Liebert AC8 generates message after all three redial attempts have
failed, dials next configured pager.
Unsuccessful Page
(Event Log)
General modem
communication problem
Liebert AC8 resets modem, generates message, redials pager up to
three more times.
Modem Reset
(Event Log)
No communication with modem
(internal hardware problem)
Liebert AC8 generates messages, makes no further dialing attempts.
Modem Internal Fault
(Active Alarm Report,
Alarm History Log)
Table 7.10
Pager dialing results
Vertiv | Liebert® AC8 User Manual | 78