EasyManuals Logo

WAGO 750 Series User Manual

WAGO 750 Series
248 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #154 background imageLoading...
Page #154 background image
150 • I/O Modules
WAGO-I/O-SYSTEM 750
Linux Fieldbus Coupler
Output Process Image
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
controls
DO 4
Channel
4
controls
DO 3
Channel
3
controls
DO 2
Channel
2
controls
DO 1
Channel
1
8 Channel Digital Output Module
750-530, -536, 753-530, -434
Output Process Image
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
controls
DO 8
Channel
8
controls
DO 7
Channel
7
controls
DO 6
Channel
6
controls
DO 5
Channel
5
controls
DO 4
Channel
4
controls
DO 3
Channel
3
controls
DO 2
Channel
2
controls
DO 1
Channel
1
8 Channel Digital Output Modules with Diagnostics and Input Process
Data
750-537
The 750-537 digital output modules have a diagnostic bit for each output
channel. When an output fault condition occurs (i.e., overload, short
circuit, or broken wire), a diagnostic bit is set. The diagnostic data is
mapped into the Input Process Image, while the output control bits are in
the Output Process Image.
Input Process Image
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Diagnost
ic bit S 7
Channel
8
Diagnost
ic bit S 6
Channel
7
Diagnost
ic bit S 5
Channel
6
Diagnost
ic bit S 4
Channel
5
Diagnost
ic bit S 3
Channel
4
Diagnost
ic bit S 2
Channel
3
Diagnost
ic bit S 1
Channel
2
Diagnosti
c bit S 0
Channel
1
Diagnostic bit S = '0' no Error
Diagnostic bit S = '1' overload, short circuit, or broken wire
Output Process Image
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
controls
DO 8
Channel
8
controls
DO 7
Channel
7
controls
DO 6
Channel
6
controls
DO 5
Channel
5
controls
DO 4
Channel
4
controls
DO 3
Channel
3
controls
DO 2
Channel
2
controls
DO 1
Channel
1

Table of Contents

Other manuals for WAGO 750 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGO 750 Series and is the answer not in the manual?

WAGO 750 Series Specifications

General IconGeneral
Protection ClassIP20
Bus CouplersPROFIBUS, CANopen, Ethernet
ModulesDigital Input, Digital Output, Analog Input, Analog Output
MountingDIN rail mounting
Voltage Supply24 V DC (typical)
Communication ProtocolDepends on the bus coupler (e.g., PROFIBUS, CANopen, DeviceNet, Ethernet)
Digital Input ChannelsVaries by module (e.g., 8, 16 channels)
Digital Output ChannelsVaries by module (e.g., 8, 16 channels)
Analog Input ChannelsVaries by module (e.g., 2, 4, 8 channels)
Analog Output Channels1, 2, 4 channels (depending on module)
Width12 mm, 24 mm (typical module widths)
Number of ChannelsVaries by module type
Current Consumption per ChannelVaries by module type

Related product manuals