Bootloader (U-Boot) 187
TFTP Server Setup
WAGO-I/O-SYSTEM 750
Linux Fieldbus Coupler
9.2 TFTP Server Setup
In order to download the Linux kernel, the file system or the boot loader, it is
essential to have a TFTP server on the development computer. Also, the user
needs to have access rights for the /tftpboot directory in the root directory:
> su
Password
> mkdir /tftpboot
> chmod 777 /tftpboot
You have to install inetd and atftp via yast2 (S.U.S.E) before you can install a
TFTP server on the development PC. After the installation, make the
following entry in the /etc/inetd.conf:
<host-ip>:tftp dgram udp wait root /usr/sbin/in.tftpd -s /tftpboot
inetd starts automatically after a reboot or it can be started manually:
> /etc/init.d/inetd start
or restarted with
> /etc/init.d/inetd stop
> /etc/init.d/inetd start

Table of Contents

Other manuals for WAGO 750 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGO 750 Series and is the answer not in the manual?

WAGO 750 Series Specifications

General IconGeneral
Protection ClassIP20
Bus CouplersPROFIBUS, CANopen, Ethernet
ModulesDigital Input, Digital Output, Analog Input, Analog Output
MountingDIN rail mounting
Voltage Supply24 V DC (typical)
Communication ProtocolDepends on the bus coupler (e.g., PROFIBUS, CANopen, DeviceNet, Ethernet)
Digital Input ChannelsVaries by module (e.g., 8, 16 channels)
Digital Output ChannelsVaries by module (e.g., 8, 16 channels)
Analog Input ChannelsVaries by module (e.g., 2, 4, 8 channels)
Analog Output Channels1, 2, 4 channels (depending on module)
Width12 mm, 24 mm (typical module widths)
Number of ChannelsVaries by module type
Current Consumption per ChannelVaries by module type

Related product manuals