Alpha/Delta (Kinetic Operator) Installation and Maintenance Manual Revision 1 - MAY 2023
119
PRELIMINARY TESTING
Table 7. SmartDC Controller Board Inputs
Terminal
No�
Label/Input
Name
Wire Connecon Uses
21 Sensor 1 N.C. input. Connecon of a Monitored
Entrapment sensor. Type of sensor is
programmable in the Installer Menu
(S1).
External entrapment sensor
connecons.
22 Sensor Common When External Entrapment Sensor
common wires are connected to this
terminal, the sensors are energized
when AC Power is present. The devic-
es are then checked for presence and
correct operaon when the open limit
is reached.
This terminal is used to per-
form monitored entrapment
check.
23 +24V DC Convenient 24VDC power for photo
eyes or the Emergency Open input.
Convenient 24VDC power
for photo eyes or Emergency
Open input.
24 Emergency Open
(Fire Dept. Open)
***
N.O. input. Emergency Open must be
enabled via Installer Menu.
It is energized by connecng
to the +24V terminal above
it. EMERG OPEN overrides
photo eye & edge sensor
commands.
*Do not connect an external control to the STOP or OPEN inputs unless the controls are located in
clear view of the enre gate area.
**Use the RADIO OPEN input or RADIO OPTIONS spade connecons for all out-of-sight controls, such
as a telephone entry or radio operated controls.
***The Fire Department Open control must be keyed or guarded so that it can only be used by
authorized personnel.