PROFIBUS DP gateway
Wieland Electric GmbH | BA000970 | 11/2016 (Rev. F)
125
Module num-
ber
Diagnosis bit
(X_Unit_Diag_Bit)
Error cause
Error message
3
0
PROFIBUS
gateway
Reserved
1
Internal error: Internal tests failed
2
Reserved
3
Reserved
4
Configuration is incompatible or invalid
5
Module state input data
6
Module state output data
7 to 31
Reserved
4
0
CANopen ga-
teway
Reserved
1
Internal error: Internal tests failed
2
Reserved
3
Reserved
4
Configuration is incompatible or invalid
5
Module state input data
6
Module state output data
7 to 31
Reserved
5
0
EtherCAT Ga-
teway
Reserved
1
Internal error: Internal tests failed
2
Reserved
3
Reserved
4
Configuration is incompatible or invalid
5
Module state input data
6
Module state output data
7 to 31
Reserved
6
0
Other module
Reserved
1
Internal error: Internal tests failed
2
Reserved
3
Reserved
4
Configuration is incompatible or invalid
5
Reserved
6 Reserved
7 to 31
Reserved
7 0 Other module Reserved
1
Internal error: Internal tests failed
2 Reserved
3
Reserved
4
Configuration is incompatible or invalid
5
Reserved
6
Reserved
7 to 31
Reserved