CANopen gateway
Wieland Electric GmbH | BA000970 | 11/2016 (Rev. F)
154
SDO 6000: Process data input objects
The 32 bytes of the process input data can be written into SDO array 6000. These are the same
data as in RxPDO 1-4 (see
PDO Communication [ch. 10.8, p. 145]
). The mapping is as follows:
Table 107: Mapping table for SDO 6000 RxPDO 1-4
SDO 6000
RxPDO
6000.1
RxPDO 1, Byte 1
6000.8
RxPDO 1, Byte 8
6000.9-16
RxPDO 2, Byte 1-8
6000.17-24
RxPDO 3, Byte 1-8
6000.25-32
RxPDO 4, Byte 1-8
SDO 6000 can only be written.
SDO 6200: Process data output objects
The 32 bytes of the process output data can be written into SDO array 6200. These are the
same data as in TxPDO 1-4 (see
PDO Communication [ch. 10.8, p. 145]
). The mapping is as
follows:
Table 108: Mapping table for SDO 6200 TxPDO 1-4
SDO 6200
TxPDO
6200.1
TxPDO 1, Byte 1
6200.8
TxPDO 1, Byte 8
6200.9-16
TxPDO 2, Byte 1-8
6200.17-24
TxPDO 3, Byte 1-8
6200.25-32
TxPDO 4, Byte 1-8
SDO 6200 can only be read.