EtherCAT Gateway
Wieland Electric GmbH | BA000970 | 11/2016 (Rev. F)
191
Notes on troubleshooting
LINK LEDs
Use the state of the LINK LEDs to check whether there is a connection to the Ethernet.
Cables
Check that the pin assignment of the used cable is correct.
Configuration
Make sure that the gateway is installed right next to the controller module and that no mo-
re than 2 samosPRO gateways are connected. Also ensure that next to the gateways only
a maximum of 12 i/o expansion modules are connected.
Mechanical strength
Check whether the RJ 45 connectors are engaged by gently pulling on the EtherCAT
connection cables.
In case of high mechanical load, secure the RJ45 cable with a tension relief.