EasyManua.ls Logo

Wieland samos PRO COMPACT - Page 38

Default Icon
200 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration of gateways
Wieland Electric GmbH | BA000970 | 11/2016 (Rev. F)
38
Tab 2: Routing table with input values (data bytes)
Transmission direction: Network/field bus -> samosPLAN5+
When you are working with several gateways: This shows the mapping (the bits used are high-
lighted in blue), while the input data for the various gateways are shown in online mode (byte
display 0x00 at the beginning of the relevant line).
Illustration 5: Routing table with input values
Tab 3: "Gateway configuration"
Tab 3 only appears when you have activated the gateway function on the SP-COP2-ENI modu-
le.
Illustration 6: "Gateway configuration" tab
NOTICE
Allocation of input and output data
The output and input data listed here refer directly to the data blocks in tab 1 and tab 2.
Output data
group
(to the PLC)
:
Only
data set 1
can be configured. This refers directly to
output data block
1
in tab 1.
Input data
group
(to the PLC)
:
Data set 1
to
data set 5
refer directly to
input data block 1
to
input data block 5
in tab
2.

Table of Contents

Related product manuals