Modbus TCP gateway
Wieland Electric GmbH | BA000970 | 11/2016 (Rev. F)
60
Error
Possible cause
Possible remedy
The SP-COP2-ENI module
does not provide any data.
Configuration required.
The configuration has not
yet been fully transmitted.
The module version of the
controller module does
not support the gateway
function.
Configure the SP-COP2-
ENI module and transfer
the configuration to the
system.
Wait until the configurati-
on has been fully transfer-
red.
Use the controller module
with the required module
version.
LED PWR/EC
Green
LED LINK
Green
LED ACT
Orange
MS LED
Red
(1 Hz)
The SP-COP2-ENI module
does not provide any data.
No data set was acti-
vated.
No Ethernet communica-
tion interface was acti-
vated.
Activate at least one data
set.
LED PWR/EC
Green
LED LINK
Green
LED ACT
Orange
MS LED
Green
The SP-COP2-ENI module
does not provide any data.
The SP-COP2-ENI module is
in the “Stop” state.
The controller module is
stopped.
Start the controller modu-
le (switch to Run mode).
LED PWR/EC
Green
MS LED
Green
(1 Hz)
The SP-COP2-ENI module
functioned correctly after
configuration but suddenly
provides no more data.
The SP-COP2-ENI module
is operated in slave mode,
the IP address is allocated
by a DHCP server.
Following a restart of the
SP-COP2-ENI module or
the DHCP server, another
address was allocated to
the SP-COP2-ENI module,
which is unknown to the
PLC.
Allocate a fixed IP
address to the SP-COP2-
ENI module.
or
Reserve a fixed IP address
for the SP-COP2-ENI mo-
dule in the DHCP server
(manual assignment usin
g
the MAC address of the
SP-COP2-ENI module).
LED PWR/EC
Green
LED LINK
Green
LED ACT
Orange
MS LED
Green
The SP-COP2-ENI / the sa-
mosPRO system is in the
“Critical error” state.
The SP-COP2-ENI module
is not properly connected
to the other modules.
The module connection
plug is dirty or damaged.
Another module in the
samosPRO system has an
internal critical error.
The voltage supply for the
SP-COP2-ENI module is
or was outside the spe-
cifications.
Plug the SP-COP2-ENI
module in correctly.
Clean the connection plug
and socket.
Switch on the power
supply again.
Check the power supply.
Check the other modules
of the samosPRO system.
LED PWR/EC
Red
LED LINK
Green
LED ACT
Orange
MS LED
Red