EasyManua.ls Logo

Wieland samos PRO COMPACT - Page 94

Default Icon
200 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EtherNet/IP gateway
Wieland Electric GmbH | BA000970 | 11/2016 (Rev. F)
94
Table 52: Feedback to the SP-COP2-ENI module for reading the data structure of the PLC-5 input
Name
Data type
Description
Data range
Type ID BYTE Data type and size Bit 0 to 3: 10 = Size spe-
cification in the next but
one byte
Bit 4 to 7: 9 = Type in the
next byte
Type ID BYTE Data type 9 = Field of the same
elements
Type ID
BYTE
Number of following bytes
1 to n+1
Type ID BYTE Data type and size Bit 0 to 3: 2 = UINT
Bit 4 to 7: 4 = Integer
Payload
UINT[n]
2n = Number of data bytes
0 to 65535
The command data of all assembly instances can be recorded using “Read input”.
In contrast to native addressing of EtherNet/IP assembly instances, the PLC-5 system address
contains an element offset which can be used.
The SP-COP2-ENI module supports fields (arrays) of UINT as PCCC data types. Due to the odd
size of the assembly instance 57, the firmware contained in the SP-COP2-ENI module assigns
an additional byte, to provide an even number of bytes.
The address scheme supported by the SP-COP2-ENI module for Read PLC-5 input is shown in
the following table:
Table 53: Read address structure of PLC-5 input
Address
Data
type
Number
of ele-
ments
Description
Data range
$N57:x UINT[n] n Input assembly of the device profile
Discrete I/O device ,
x = 0 to 33, n = 34 - x
Element 1 to 33:
0 to 65535
Element 34 Bit 0 to 7
(LSB): 0x00, 0x40,
0x80, 0xc0
Element 34 Bit 8 to 15
(MSB): 0
$N167:x UINT[n] n
Input assembly of:
Logic input bits
(n = 1-x to 25-x, x = 0 to 24)
0 to 65535
System state and system mode
(n = 26-x, x = 0 to 25)
Bit 0 to 7 (LSB):
System mode (1, 2, 3,
4, 5, 7, 21)
Bit 8 to 15 (MSB):
System state (0x00,
0x40, 0x80, 0xc0)
State bytes of the controller module
(n = 27-x to 56-x, x = 26 to 55)
0 to 65535
Example: “$N57:10” and “Total Transaction = 24” address elements 11 to 34 correspond to
bytes 20 to 66 of assembly instance 57.
Note: Byte 67, which is not specified in assembly instance 57, is also transferred.
Note: The position of the word data with system state and system mode are dependent on the
requested amount of data “x”.
1127364491

Table of Contents

Related product manuals