No. Name Unit Default Settings
–
Model CIMR-Po
– 2A0110 2A0138 2A0169 2A0211
o2-04 Drive Model Selection Hex. 70 72 73 74
E2-11 Motor Rated Power kW (HP)
30
(40)
37
(50)
45
(60)
55
(75)
b3-04 V/f Gain during Speed Search % 80 80 80 80
b3-06 Output Current 1 during Speed Search – 0.5 0.5 0.5 0.5
b3-07
Output Current 2 during Speed Search
(Speed Estimation Type)
– – – – –
b3-26 Start Speed Search Select – – – – –
b8-03 Energy Saving Control Filter Time Constant s 0.50 0.50 0.50 2.00
b8-04 Energy Saving Coefficient Value – 46.27 38.16 35.78 31.35
C5-17 Motor Inertia
kgm
2
0.220 0.273 0.333 0.490
C6-02 Carrier Frequency Selection – 7 7 7 7
E2-01 Motor Rated Current A 105 131 160 190
E2-02 Motor Rated Slip Hz 1.8 1.33 1.6 1.43
E2-03 Motor No-Load Current A 21.9 38.2 44 45.6
E2-05 Motor Line-to-Line Resistance Ω 0.064 0.039 0.03 0.022
E2-06 Motor Leakage Inductance % 20.8 18.8 20.2 20.5
E2-10 Motor Iron Loss for Torque Compensation W 699 823 852 960
L2-02 Momentary Power Loss Ride-Thru Time s 2 2 2 2
L2-03 Momentary Power Loss Minimum Baseblock Time s 1.1 1.1 1.2 1.3
L2-04 Momentary Power Loss Voltage Recovery Ramp Time s 0.6 0.6 1 1
L3-24 Motor Acceleration Time for Inertia Calculations s 0.323 0.32 0.387 0.317
L8-02 Overheat Alarm Level °C 130 130 130 125
L8-35 Installation Method Selection – 0 0 0 0
L8-38 Carrier Frequency Reduction Selection – 2 2 2 2
n1-03 Hunting Prevention Time Constant ms 10 10 10 10
B.16 Defaults by Drive Model
490
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual