No. Name Unit Default Settings
–
Model CIMR-Po
– 4A0675 4A0930 4A1200
o2-04 Drive Model Selection Hex. AE B0 B2
E2-11 Motor rated power kW (HP)
355
(500
-550)
500
(750)
630
(1000)
b3-04 V/f Gain during Speed Search % 60 60 60
b3-06 Output Current 1 during Speed Search – 0.7 0.7 0.7
b3-07
Output Current 2 during Speed Search
(Speed Estimation Type)
– – 2.0 2.0
b3-26 Start Speed Search Select – – 1000 1000
b8-03 Energy Saving Control Filter Time Constant s 2.00 2.00 2.00
b8-04 Energy Saving Coefficient Value – 23.84 20.26 17.06
C5-17 Motor Inertia
kgm
2
12.00 14.00 18.00
C6-02 Carrier Frequency Selection – 7 7 7
E2-01 Motor Rated Current A 650 900 1200
E2-02 Motor Rated Slip Hz 1 0.9 0.7
E2-03 Motor No-Load Current A 130 180 240
E2-05 Motor Line-to-Line Resistance Ω 0.012 0.009 0.006
E2-06 Motor Leakage Inductance % 20 20 20
E2-10 Motor Iron Loss for Torque Compensation W 5560 7833 11123
L2-02 Momentary Power Loss Ride-Thru Time s 2 2 2
L2-03 Momentary Power Loss Min. Basebl. Time s 2.3 3.1 4.6
L2-04 Momentary Power Loss Volt. Recov. Time s 1 3 4.5
L3-24 Motor Acceleration Time for Inertia Calculations s 1.667 2.222 3.333
L8-02 Overheat Alarm Level °C 140 140 140
L8-35 Installation Method Selection – 0 0 0
L8-38 Carrier Frequency Reduction Selection – 2 2 2
n1-03 Hunting Prevention Time Constant ms 100 100 100
Table B.8 600 V Class Drives Default Settings by Drive Model
No. Name Unit
–
Model CIMR-Po
– 5A0003 5A0004 5A0006 5A0009 5A0011
o2-04 Drive Model Selection Hex. C3 C4 C5 C7
E2-11 Motor Rated Power
kW
(HP)
1.5
(2)
2.2
(3)
3.7
(5)
5.5
(7.5)
7.5
(10)
b3-04 V/f Gain during Speed Search % 100 100 100 100 100
b3-06 Output Current 1 during Speed Search – 0.5 0.5 0.5 0.5 0.5
b3-07
Output Current 2 during Speed Search
(Speed Estimation Type)
– – – – – –
b3-26 Start Speed Search Select – – – – – –
b8-03 Energy Saving Control Filter Time Constant s 0.50 0.50 0.50 0.50 0.50
b8-04 Energy Saving Coefficient Value – 494.4 415.3 320.2 239.95 199.86
C5-17 Motor Inertia
kgm
2
0.0068 0.0088 0.0158 0.0255 0.037
C6-02 Carrier Frequency Selection – 7 7 7 7 7
E2-01 Motor Rated Current A 2.7 3.9 6.1 9 11
E2-02 Motor Rated Slip Hz 2.5 3.0 2.7 1.5 1.3
E2-03 Motor No-Load Current A 0.8 1.2 1.8 2.7 3.3
E2-05 Motor Line-to-Line Resistance Ω 13.72 8.825 4.936 2.601 1.446
E2-06 Motor Leakage Inductance % 18.3 18.7 19.3 18.2 15.5
E2-10 Motor Iron Loss for Torque Compensation W 53 77 130 193 263
L2-02 Momentary Power Loss Ride-Thru Time s 0.2 0.3 0.5 0.5 0.8
L2-03
Momentary Power Loss Minimum Baseblock
Time
s 0.5 0.5 0.8 0.8 1
B.16 Defaults by Drive Model
498
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual